38/66kV High Voltage Cable: Specifications and Selection Guide

28, Oct. 2026

 

38/66kV High Voltage Cable: Specifications and Selection Guide

A 38/66kV high voltage cable is specified by its rated voltage: 38 kV between conductor and earth, and 66 kV between conductors. In the common U0/U (Um) notation, this is generally written as 38/66 (72.5) kV, where 72.5 kV is the highest system voltage for which the equipment is designed. Buyers should select the cable by matching this rating and its construction to the network’s earthing arrangement, installation conditions, load, and applicable project standard. The voltage label alone is not enough to confirm that a cable is suitable.

Read more

Who This Guide Is For

This guide is for utility engineers, EPC contractors, distributors, and procurement teams evaluating 38/66kV cable for transmission or distribution projects. It explains the main construction options, the information to include in a technical inquiry, and the supplier details to verify before ordering. It is intended as a purchasing and specification overview, not a replacement for network studies, engineering design, or the project’s governing standards.

What a 38/66kV Cable Does

Voltage designation and cable construction

High voltage cable transfers electrical power between substations, switchyards, generating facilities, and other parts of a power network. A typical 38/66kV design uses a conductor, conductor screen, XLPE insulation, insulation screen, metallic screen or sheath, and an outer protective sheath. The layers work together to carry current, control the electric field, provide an earth-fault current path where designed, and protect the cable from its installation environment.

In the U0/U (Um) designation, U0 is the rated power-frequency voltage between conductor and earth, U is the rated voltage between conductors, and Um is the highest system voltage. For this voltage class, these values are 38 kV, 66 kV, and 72.5 kV respectively. Always check how the project specification states the voltage class, since naming conventions and required cable designs can differ by market and standard.

Common material and design options

Conductors are commonly made from copper or aluminium. Copper offers higher conductivity for a given conductor size, while aluminium can be considered where conductor weight, material choice, and project design favour it; the required cross-section must be calculated for the actual load and installation. XLPE is a widely used insulation material for this class, but the complete cable design must also account for screens, metallic layers, water protection, and the outer sheath.

Metallic screen and sheath arrangements vary with the system’s earthing and bonding design. Options may include copper wires or tapes and, where specified, additional moisture barriers or protective layers. These details affect fault-current capacity, induced losses, bonding requirements, and installation, so they should be agreed with the project engineer rather than selected solely from a catalogue description.

Specifications to Confirm Before Ordering

Electrical and thermal requirements

Start with the voltage designation, system frequency, earthing method, expected load, and short-circuit conditions. For XLPE cable designs commonly based on relevant IEC requirements, 90°C is a typical maximum conductor temperature during normal operation, and 250°C is a commonly applied maximum conductor temperature under short-circuit conditions. These are design limits, not a guarantee of the current rating: the permitted load depends on conductor size, installation method, soil or ambient conditions, grouping, and bonding arrangement.

Ask the supplier to identify the applicable standard and the exact edition or project specification used for the design. IEC 60840 is one commonly referenced standard for extruded-insulation power cables and accessories in its specified voltage range, but the project may require national standards, additional utility requirements, or specific approved designs. Confirm that the standard applies to the complete cable and accessories package as required by the contract.

If you want to learn more, please visit our website Zhongdong Cable Co., Ltd..

Construction and installation data

Define conductor material and cross-section, conductor shape, insulation thickness, metallic screen construction, sheath material, and any required water-blocking features. State whether the cable will be installed directly buried, in ducts, tunnels, trays, or another environment. Include route length, pulling conditions, minimum bending radius requirements, expected exposure to moisture or chemicals, and any mechanical protection needs.

For single-core AC cables, bonding is an important design decision. The screen bonding arrangement can influence induced voltage and sheath losses, so the cable specification should align with the project’s earthing and bonding study. Also confirm the accessory scope, including joints and terminations, because compatibility with the cable insulation diameter and screen design is essential.

How to Select the Right Cable

A practical selection framework

  1. Confirm the network rating. Provide U0, U, Um, frequency, and the system earthing arrangement. Ask the engineer to confirm that the selected voltage class is appropriate for the network.
  2. Establish the electrical duty. Share continuous load, overload expectations, short-circuit current, and fault duration. These inputs support conductor sizing and verification of screen and metallic-layer capacity.
  3. Describe installation conditions. Provide route drawings or dimensions, installation method, ambient or soil conditions, grouping, and route length. These factors are needed to assess ampacity and installation constraints.
  4. Specify construction and accessories. Select conductor material, metallic screen and sheath design, outer sheath, water protection, and the required joints and terminations. Make the interface requirements explicit.
  5. Review documentation and delivery scope. Request the technical datasheet, applicable standard, routine test documentation required by the contract, packaging details, and a delivery schedule. Compare offers on an equivalent scope rather than on cable price alone.

Common selection mistakes

A frequent mistake is choosing a conductor cross-section based only on nominal load current. Cable rating can change with burial depth, soil thermal properties, duct configuration, grouping, and bonding, so the rating should be checked against the actual route. Another mistake is omitting short-circuit duty or specifying a screen without stating the fault-current requirement.

Buyers should also avoid treating a voltage designation as a complete specification. Two cables labelled 38/66kV may differ in conductor, screen, sheath, water protection, test requirements, and accessory compatibility. Request a clause-by-clause technical review when supplier quotations use different standards or construction descriptions.

Pricing, MOQ, and Lead Time

The price of a 38/66kV cable depends on the conductor material and size, cable construction, order length, raw-material pricing, accessories, testing scope, and delivery destination. A technically comparable quotation should state the cable specification, unit of measure, quantity, packaging, Incoterm or delivery basis, and whether joints or terminations are included. Shorter or non-standard production quantities may be subject to manufacturing and commercial review, so buyers should confirm any minimum order requirements directly.

Lead time depends on design approval, material availability, production scheduling, testing, and shipping arrangements. We recommend requesting a project-specific schedule that separates technical approval, production, inspection, and dispatch milestones. Providing complete route and specification information early can reduce clarification cycles, but no delivery date should be assumed until it is confirmed in the supplier’s offer.

Supplier Evaluation Checklist

  • Does the supplier identify the voltage designation, applicable standard, and cable construction clearly?
  • Can the supplier review the conductor, screen, and sheath requirements against the project data provided?
  • Are routine and other required tests, inspection arrangements, and documentation stated in the offer?
  • Are cable accessories included, excluded, or quoted separately, with compatibility requirements specified?
  • Does the quotation define quantity, packaging, delivery basis, production schedule, and any order restrictions?

Request a datasheet and compliance review against your own specification, rather than relying only on a generic product description. Where the project has special requirements, submit them as a deviation schedule and ask the supplier to identify each point as compliant, non-compliant, or requiring clarification. This makes technical and commercial comparisons more reliable.

Key Takeaways

  • 38/66kV generally refers to U0/U (Um) values of 38/66 (72.5) kV.
  • Voltage class, conductor size, metallic screen, sheath, and accessories must be specified for the actual network and installation.
  • Thermal ratings depend on installation and project conditions; verify them through engineering calculations rather than assuming a catalogue value.
  • Compare suppliers on construction, standards, testing, documentation, accessories, and delivery scope as well as price.

Conclusion: Next Steps for Buyers

The right 38/66kV high voltage cable is the design that matches the network rating, electrical duty, installation route, and project specification—not simply a cable carrying the correct voltage label. Before issuing a purchase order, confirm the voltage designation, loading and fault data, cable construction, bonding approach, accessory scope, applicable standards, and required documentation with the project engineer. Zhongdong Cable Co., Ltd. can review your project requirements and prepare a cable proposal for technical and commercial evaluation. Send us your specification, quantity, route conditions, and target delivery location to begin an inquiry.